Development of recommendations to support the level of reactive power compensation in electrical networks
Content
- Introduction
- 1. Relevance of the topic
- 2. The scientific importance
- 3. Modern reactive power compensation devices
- 4. A review of research and development on the subject.
- 5. The final part
- References
Introduction
In modern times become acutely the question of energy savings. For most industrial electrical power is the primary source of energy. So to get the issue of reducing transmission losses and power consumption. In many areas there is a process of development of energy-saving technologies aimed at efficient use of industrial systems and processing plants. The main power consumers in any enterprise are: electric motors and transformers. Their principle of operation is based on the creation of an electromagnetic field, which requires the consumption of reactive power. But does not produce reactive power of useful work, but only leads to an additional load lines, which reduces the power factor, leading to an increase in active power losses due to heat conductors. Also, the presence of reactive power level affects the voltage and power quality, which leads to additional losses in the conductors, increasing the charge power supplier, etc.
1. Relevance of the topic
The relevance of the topic is determined by the need to reduce customer costs by reducing the consumption of reactive power and reduce possible with compensating devices - correction systems, synchronous condensers, STK - which are installed on the tires low voltage substation consumer. These devices can reduce the cost for the consumption of reactive power and voltage increase tire substation.
2. The scientific importance
The cost of electricity is a significant part of the cost of production. Therefore, reactive power compensation, which will reduce energy losses and reduce the company's costs for its consumption, has expediency and is one of the priorities in the development of energy-saving technologies
3. Modern reactive power compensation devices
To improve energy efficiency need to use more fuel-efficient ways of generation, transmission and consumption. Exceptions are the factors leading to the emergence of losses, will lead to a more rational use of electrical systems. One solution to this problem is to increase the power factor. Is most effective at compensating devices connected as close as possible to the inductive load.
The most promising means of reactive power compensation active-inductive loads are cosine capacitors and capacitor banks (CS). Condensing units are widely used in network and power supply systems and industrial enterprises of power virtually all levels not only in the form of individual, group and centralized power factor correction (PM), as well as baluns, filters, combined (symmetry-balancing, filtering and baluns, etc. etc.) devices, capacitive transducers parameters of electric power, etc. In general, the state of CG medium voltage in Ukraine, can be described as deplorable: mostly unregulated KU, without proper protective equipment (reactors and so on.), Often with environmentally harmful capacitors (impregnated trichlorodiphenyl), produced until the mid 80's . requiring immediate replacement and special disposal. The task of the introduction of modern high-efficiency CHP is becoming more urgent.
European manufacturers of condensing units have achieved a high level and can offer a capacitor-frequency power reaches 1MVar with nominal voltages up to 24kV.
Schemes switching capacitors in the star used in installations with a continuously variable PM (containing a thyristor controlled reactors) and filtrokompensiruschih devices comprising one or several chains of series-connected capacitors and reactors of filter tuned to the specific frequency of the higher harmonic components. These settings allow for simultaneous compensation of RM, partial suppression present in compensated networks harmonics that distort the sinusoidal voltage and other functions. KU single-phase adjustable choke dekompensiruyuschim applied on voltage 27 kV (for railways). KU series compensation capacitors can be manufactured with high overload capabilities. Three-phase and cosine filter capacitors usually issued up to a voltage of 12 kV. In automatic KU with a rated voltage of 12.6 kV often use a stepwise inclusion of three-phase capacitors, although in some cases more effective is the inclusion of single-phase capacitors in the star. Switching levels KU, usually produced by vacuum contactors. To reduce the inrush current during switching launchers used (damping) Reactors (English - inrush reactors), commercially available from 0.05-0.1 mH inductors for nominal currents of capacitors 50-200 A.
In an increasing number of cases, the use of CG in a degraded the quality of electricity in accordance with GOST 13109-97 are commonly used:
In today's security systems KU, working in conditions of deviations and non-sinusoidal voltage devices are used (blocks) control:
For registration and the proper functioning of the protection KU commonly used flexible devices at the same time asking for all of the control functions. At the same time, partial control can perform both individual devices and modern regulators capacity KU. Last, commonly called "power factor controllers", including can control how THDU, and THDІ, as well as individual harmonic components of domestic current KU (with such adjustments are respectively two inputs for measuring circuits). Regulators are also applied without control of its own current KU, calculating overcurrent corresponding level of regulation largest THDU. In the case of considering the simultaneous exposure to the elements KU several indicators of the quality of electricity in the protection device or controller KU important to have the possibility of correcting the maximum current value: for example, reduced voltage can be tolerated somewhat too high overload currents harmonic elements, etc. It should be noted that the sensitivity current regulator has reached the 2 mA. Electrical Market in Ukraine, especially in recent times, brimming with new modifications of regulators, differing not only the components and functions, but also new approaches to the construction of the control algorithms. In most cases, conventional regulators based algorithm is to regulate the magnitude and sign of RM, which is usually determined by the current of one phase and a line voltage between the other two phases of three-phase network. In the case of unbalance voltage / current, current transformers, as is generally done in phase with minimal current (in order to avoid overcompensation mode in the other phases), although this appears appropriate underdosing RM. To compensate for the RM significantly asymmetric modes should be used single-ended circuits KU, including circuit consisting of three groups of single-phase capacitors of different capacities, which are governed by special algorithms special types of regulators [1,2].
4. A review of research and development on the subject.
Method of
calculating the optimum power compensation systems mimnimum terms of
reduced costs [3,4,5].
The calculation for
the SS "Commune".
Where
Зmin the
minimum cost;
Ен
– the coefficient of the
economic efficiency of capital investments, taking 0.25;
Кку
и
КВ
– the cost of KU and switches,
respectively
Иconst
– fixed costs;
Иvar
– variable costs;
П
– charge for reactive power
flows..
According to the
daily (winter and summer) load schedule PS "commune" is
determined daily fee of RM flows at different power ratings KU.
SS | Qky, MVar*h | 7-22 h. | с 23-6 h. | Wp, MW*h | tgϕ | Kϕ | П1, thnd.grn | П2, thnd.grn | П, thnd.grn | ΣПw | ||
WQ п, MVar*h | WQ ген, MVar*h | WQ п, MVar*h | WQ ген, MVar*h | |||||||||
Communa | 0,9 | 0 | 3,43 | 0 | 2,9 | 26,6 | -0,24 | 1 | 0,17748 | 0 | 0,17748 | 37,8 |
0,75 | 0 | 1,18 | 0 | 1,55 | 26,6 | -0,10 | 1 | 0,09486 | 0 | 0,09486 | 20,2 | |
0,6 | 3,32 | 0 | 1,18 | 0,03 | 26,6 | 0,17 | 1 | 0,093636 | 0 | 0,093636 | 19,9 | |
0,45 | 6,81 | 0 | 2,59 | 0 | 26,6 | 0,35 | 1,01 | 0,19176 | 0,001918 | 0,193678 | 41,3 | |
0,3 | 5,57 | 0 | 2,54 | 0 | 26,6 | 0,30 | 1,0025 | 0,165444 | 0,000414 | 0,165858 | 35,3 | |
0,15 | 7,82 | 0 | 3,85 | 0 | 26,6 | 0,44 | 1,0361 | 0,238068 | 0,008594 | 0,246662 | 52,5 | |
0 | 10,07 | 0 | 5,2 | 0 | 26,6 | 0,57 | 1,1024 | 0,311508 | 0,031898 | 0,343406 | 73,1 |
SS | Qky, MVar*h | 7-22 h. | с 23-6 h. | Wp, MW*h | tgϕ | Kϕ | П1, thnd.grn | П2, thnd.grn | П, thnd.grn | ΣПw | ||
WQ п, MVar*h | WQ ген, MVar*h | WQ п, MVar*h | WQ ген, MVar*h | |||||||||
Communa | 0,9 | 1,14 | 1,51 | 0,43 | 1,91 | 29,9 | -0,06 | 1 | 0,14892 | 0 | 0,14892 | 22,63584 |
0,75 | 2,49 | 0,61 | 0,88 | 1,01 | 29,9 | 0,06 | 1 | 0,13056 | 0 | 0,13056 | 19,84512 | |
0,6 | 4,13 | 0 | 1,33 | 0,11 | 29,9 | 0,18 | 1 | 0,118116 | 0 | 0,118116 | 17,95363 | |
0,45 | 6,38 | 0 | 2,57 | 0 | 29,9 | 0,30 | 1,0025 | 0,18258 | 0,000456 | 0,183036 | 27,82154 | |
0,3 | 8,63 | 0 | 3,92 | 0 | 29,9 | 0,42 | 1,0289 | 0,25602 | 0,007399 | 0,263419 | 40,03968 | |
0,15 | 10,88 | 0 | 5,27 | 0 | 29,9 | 0,54 | 1,0841 | 0,32946 | 0,027708 | 0,357168 | 54,28947 | |
0 | 13,13 | 0 | 6,62 | 0 | 29,9 | 0,66 | 1,1681 | 0,4029 | 0,067727 | 0,470627 | 71,53538 |
SS | Qky, MVar*h | 7-22 h. | с 23-6 h. | Wp, MW*h | tgϕ | Kϕ | П1, thnd.grn | П2, thnd.grn | П, thnd.grn | ΣПw | ||
WQ п, MVar*h | WQ ген, MVar*h | WQ п, MVar*h | WQ ген, MVar*h | |||||||||
Communa | 0,9 | 1,35 | 0,3 | 2,16 | 0,06 | 65,9 | 0,05 | 1 | 0,075276 | 0 | 0,075276 | 16,03 |
0,75 | 3,48 | 0,03 | 3,45 | 0 | 65,9 | 0,10 | 1 | 0,141372 | 0 | 0,141372 | 30,11 | |
0,6 | 5,73 | 0 | 4,8 | 0 | 65,9 | 0,16 | 1 | 0,214812 | 0 | 0,214812 | 45,75 | |
0,45 | 7,98 | 0 | 6,15 | 0 | 65,9 | 0,21 | 1 | 0,288252 | 0 | 0,288252 | 61,40 | |
0,3 | 10,23 | 0 | 7,5 | 0 | 65,9 | 0,27 | 1,0004 | 0,361692 | 0,000145 | 0,361837 | 77,07 | |
0,15 | 12,42 | 0 | 8,85 | 0 | 65,9 | 0,32 | 1,0169 | 0,433908 | 0,007333 | 0,441241 | 93,98 | |
0 | 14,73 | 0 | 10,2 | 0 | 65,9 | 0,38 | 1,1225 | 0,508572 | 0,0623 | 0,570872 | 121,60 |
SS | Qky, MVar*h | 7-22 h. | с 23-6 h. | Wp, MW*h | tgϕ | Kϕ | П1, thnd.grn | П2, thnd.grn | П, thnd.grn | ΣПw | ||
WQ п, MVar*h | WQ ген, MVar*h | WQ п, MVar*h | WQ ген, MVar*h | |||||||||
Communa | 0,9 | 0 | 3,89 | 0,5 | 2,15 | 24,7 | -0,22 | 1 | 0,14178 | 0 | 0,14178 | 21,6 |
0,75 | 0,18 | 1,06 | 0,7 | 0,55 | 24,7 | -0,03 | 1 | 0,051612 | 0 | 0,051612 | 7,8 | |
0,6 | 1,06 | 0,44 | 1,06 | 0 | 24,7 | 0,07 | 1 | 0,043248 | 0 | 0,043248 | 6,6 | |
0,45 | 3,16 | 0,29 | 2,41 | 0 | 24,7 | 0,21 | 1 | 0,113628 | 0 | 0,113628 | 17,3 | |
0,3 | 5,26 | 0,14 | 3,76 | 0 | 24,7 | 0,36 | 1,0121 | 0,184008 | 0,002226 | 0,186234 | 28,3 | |
0,15 | 7,36 | 0 | 5,11 | 0 | 24,7 | 0,50 | 1,0625 | 0,254388 | 0,015899 | 0,270287 | 41,1 | |
0 | 9,61 | 0 | 6,46 | 0 | 24,7 | 0,65 | 1,16 | 0,327828 | 0,052452 | 0,38028 | 57,8 |
The calculation of
variable costs, is charge power losses in the system. Taking into
account only the loss in transformers substations.
Annual electricity
losses calculated by the formula:
где
-
losses
in the windings of the transformer,
ΔРст
– iron
loss
transformer.
Number of
hours of maximum losses τm defined by the formula:
where
Тм
– the number of hours of use
of the maximum load.
The value of Tm is
determined from the annual electricity consumption
где
Рmax
– maximum power.
For the conditions
of the Donbass accepted that the number of winter days in a year is
213 days, and the summer - 152, then [6,7]:
The value of
Tm and τm Transformer Substation "The Commune"
is shown in the Table. 5
Тр-р |
Daily consumption of e / p, MWh |
Wyear, MWh |
Рмax, MWh |
Тм, h |
τм, h |
|
|
Winter |
Summer |
|
|
|
|
Т1 |
26,6 |
29,9 |
10210,6 |
2,08 |
4908,9 |
3312,1 |
Т2 |
65,9 |
24,7 |
17791,1 |
3,76 |
4731,7 |
3123,9 |
The results of
calculation of annual energy losses are given in Tables 6 and 7.
Qky | Pmax | Qmax | S, MWh | dPмd, kWh | dWt, MWh | Иvar, thnd. |
0,9 | 2,08 | 1,09 | 2,09 | 1,544 | 120,68 | 82,1 |
0,75 | 2,08 | 1,09 | 2,11 | 1,572 | 120,82 | 82,2 |
0,6 | 2,08 | 1,09 | 2,14 | 1,617 | 121,04 | 82,3 |
0,45 | 2,08 | 1,09 | 2,18 | 1,677 | 121,33 | 82,5 |
0,3 | 2,08 | 1,09 | 2,22 | 1,752 | 121,70 | 82,8 |
0,15 | 2,08 | 1,09 | 2,28 | 1,844 | 122,15 | 83,1 |
0 | 2,08 | 1,09 | 2,35 | 1,952 | 122,68 | 83,4 |
Qky | Pmax | Qmax | S, MWA | dPмд, kW | dWt, MWh | Иvar, thnd. |
0,9 | 3,76 | 1,09 | 3,76 | 3,60 | 130,13 | 88,5 |
0,75 | 3,76 | 1,09 | 3,78 | 3,62 | 130,23 | 88,6 |
0,6 | 3,76 | 1,09 | 3,79 | 3,65 | 130,38 | 88,7 |
0,45 | 3,76 | 1,09 | 3,81 | 3,69 | 130,58 | 88,8 |
0,3 | 3,76 | 1,09 | 3,84 | 3,75 | 130,84 | 89,0 |
0,15 | 3,76 | 1,09 | 3,88 | 3,82 | 131,15 | 89,2 |
0 | 3,76 | 1,09 | 3,91 | 3,89 | 131,52 | 89,4 |
Results costing 3
are shown in Table 8 and 9.
Qky | Kky | Kв | Иconst | Иvar | П | 3 |
0,9 | 50,032 | 32 | 11,81261 | 82,06308 | 60,43908 | 174,8228 |
0,75 | 62,606 | 64 | 18,23126 | 82,15703 | 40,0503 | 172,0901 |
0,6 | 56,376 | 64 | 17,33414 | 82,30414 | 37,8981 | 167,6304 |
0,45 | 34,418 | 32 | 9,564192 | 82,50444 | 69,07487 | 177,748 |
0,3 | 28,188 | 32 | 8,667072 | 82,75791 | 75,36736 | 181,8393 |
0,15 | 21,196 | 32 | 7,660224 | 83,06456 | 106,8285 | 210,8523 |
0 | 0 | 0 | 0 | 83,42438 | 144,6809 | 228,1053 |
Qky | Kky | Kв | Иconst | Иvar | П | 3 |
0,9 | 50,032 | 32 | 11,81261 | 88,49153 | 37,58 | 158,3965 |
0,75 | 62,606 | 64 | 18,23126 | 88,5565 | 37,96 | 176,3965 |
0,6 | 56,376 | 64 | 17,33414 | 88,65825 | 52,33 | 188,415 |
0,45 | 34,418 | 32 | 9,564192 | 88,79677 | 78,67 | 193,6346 |
0,3 | 28,188 | 32 | 8,667072 | 88,97207 | 105,38 | 218,065 |
0,15 | 21,196 | 32 | 7,660224 | 89,18415 | 135,07 | 245,2114 |
0 | 0 | 0 | 0 | 89,433 | 179,40 | 268,8314 |
Construct the
dependence of costs on the power W KU.
From figure it can
be concluded that the optimum power for KU is Qbk T1 = 0.6 Mvar.
The novelty of this work lies in a comprehensive approach to solving the problem of reactive power compensation. The technique and the program will select the optimal use of capacitor banks. Thus, when considering the level of cost KU, installation is economically feasible. Further research is necessary to determine the optimal amount of regulatory effectiveness ratio, the rules on maintenance payments KU, the cost of electricity consumed. On the moment of writing this abstract the master's work was not completed. Its final variant can be obtained from the author or the scientific adviser after December 2013.
5.The final part
References